SEER2, EER2, HSPF2 and the federal minimums

What each rating measures, the DOE minimum for your state, and what ENERGY STAR and Cold Climate require on top.

Checked against the sources below on October 7, 2026

The short answer

A split heat pump has to be at least 14.3 SEER2 and 7.5 HSPF2 anywhere in the country. ENERGY STAR starts at 15.2 SEER2, 11.0 EER2 and 7.8 HSPF2. And every one of those numbers belongs to a specific indoor/outdoor pair — the same outdoor unit can clear a threshold with one indoor unit and miss it with another.

What each rating measures

RatingWhat it isRead it as
SEER2Seasonal cooling efficiency: cooling delivered over a season divided by the electricity used.The cooling-bill number. Higher is better.
EER2Cooling efficiency at one fixed condition: 95°F outdoors.The hot-afternoon number. It is why the Southwest has its own minimum.
HSPF2Seasonal heating efficiency of a heat pump.The heating-bill number. Higher is better.
COP @ 5°FHeat delivered divided by electricity used, at 5°F outdoors. No units.The cold-climate number. 1.75 means 1.75 units of heat per unit of electricity.

The “2” means the rating was measured under the current federal test procedure, in force since 2023, which tests against more duct resistance than the old one. A SEER2 number is lower than the SEER number the same equipment would have carried — the two are not interchangeable.

The federal minimum

The national standard applies to equipment manufactured on or after January 1, 2023. For heat pumps it is the only standard: there is no regional heat pump minimum.

ProductSEER2HSPF2
Split-system heat pump14.37.5
Single-package heat pump13.46.7
Split-system air conditioner13.4—
Single-package air conditioner13.4—
10 CFR 430.32(c)(5). Small-duct high-velocity and space-constrained products have their own lower values.

Air conditioners: three regions

Air conditioners installed in the Southeast or Southwest on or after January 1, 2023 have to meet a higher bar, and the Southwest adds an EER2 floor. In the North the national number applies.

Alaska: NorthAKMaine: NorthMEWisconsin: NorthWIVermont: NorthVTNew Hampshire: NorthNHWashington: NorthWAIdaho: NorthIDMontana: NorthMTNorth Dakota: NorthNDMinnesota: NorthMNIllinois: NorthILMichigan: NorthMINew York: NorthNYMassachusetts: NorthMAOregon: NorthORNevada: SouthwestNVWyoming: NorthWYSouth Dakota: NorthSDIowa: NorthIAIndiana: NorthINOhio: NorthOHPennsylvania: NorthPANew Jersey: NorthNJConnecticut: NorthCTRhode Island: NorthRICalifornia: SouthwestCAUtah: NorthUTColorado: NorthCONebraska: NorthNEMissouri: NorthMOKentucky: SoutheastKYWest Virginia: NorthWVVirginia: SoutheastVAMaryland: SoutheastMDDelaware: SoutheastDEArizona: SouthwestAZNew Mexico: SouthwestNMKansas: NorthKSArkansas: SoutheastARTennessee: SoutheastTNNorth Carolina: SoutheastNCSouth Carolina: SoutheastSCDistrict of Columbia: SoutheastDCOklahoma: SoutheastOKLouisiana: SoutheastLAMississippi: SoutheastMSAlabama: SoutheastALGeorgia: SoutheastGAHawaii: SoutheastHITexas: SoutheastTXFlorida: SoutheastFLPuerto Rico: SoutheastPR
North30 states and territoriesSoutheast18 states and territoriesSouthwest4 states and territories
Air conditionerSoutheastSouthwestSouthwest EER2
Split AC, under 45,000 Btu/h14.3 SEER214.3 SEER211.7 EER2 (9.8 if SEER2 is 15.2 or higher)
Split AC, 45,000 Btu/h and up13.8 SEER213.8 SEER211.2 EER2 (9.8 if SEER2 is 15.2 or higher)
Single-package AC13.4 SEER2 (national)13.4 SEER2 (national)10.6 EER2
10 CFR 430.32(c)(6). EER2 is measured at 95°F outdoor dry-bulb.

Southeast: Kentucky, Virginia, Maryland, Delaware, Arkansas, Tennessee, North Carolina, South Carolina, District of Columbia, Oklahoma, Louisiana, Mississippi, Alabama, Georgia, Hawaii, Texas, Florida, Puerto Rico, and the U.S. territories. Southwest: Nevada, California, Arizona, New Mexico. North: every other state.

The rule that makes the pair matter

The regulation says that any model of outdoor unit that has a certified combination with a rating below the standard for a region cannot be installed in that region. The compliance question is not “what does this outdoor unit rate?” — it is “what does this outdoor unit rate with its least efficient certified match?”

ENERGY STAR, and Cold Climate above it

Efficiency tiers on a certified pairA four-rung ladder. Bottom: the federal minimum, nationwide SEER2 14.3 and HSPF2 7.5 for heat pumps, regional for air conditioners. Then ENERGY STAR version 6.2: split heat pump SEER2 15.2, EER2 11.0, HSPF2 7.8, certified per pair. Then ENERGY STAR Cold Climate: HSPF2 8.5 non-ducted or 8.1 ducted, COP at least 1.75 at 5 degrees, capacity at 5 degrees at least 70 percent of 47 degrees, with controls verification. Top: ENERGY STAR Most Efficient, revised yearly.THE EFFICIENCY LADDERwhat each mark on a certified pair means — and which rebate looks at which rungENERGY STAR Most Efficientthe year’s top tier — criteria revised every yearcheck the current list; do not memorize a numberpremium rebates · marketing claimENERGY STAR Cold Climate+ HSPF2 ≥ 8.5 non-ducted / 8.1 ducted+ COP ≥ 1.75 at 5 °F · capacity at 5 °F ≥ 70% of 47 °F+ controls verification (real controls, not a forced speed)cold-climate incentives · NEEP list (v4.0) for Northeast utilitiesENERGY STAR (Heat Pump v6.2)split heat pump: SEER2 ≥ 15.2 · EER2 ≥ 11.0 · HSPF2 ≥ 7.8certified per indoor/outdoor PAIR, as testedwhere most utility rebates startFederal minimum (DOE 2023, Appendix M1)heat pumps, nationwide: SEER2 14.3 · HSPF2 7.5air conditioners: North 13.4 · Southeast/Southwest 14.3 (+ EER2 floor in the Southwest)legal to install — the floor, not a selling pointmore efficient · more paperworkIn the lookup tool, every certified pair carries its ENERGY STAR, Cold Climate and Most Efficient flags — read the flag of the PAIR, not the box.The federal 25C/25D tax credits ended for equipment placed in service after Dec 31, 2025; utility and state programs use these tiers now.
Four rungs. The federal minimum is what is legal to sell; the ones above it are what rebate programs look at.

ENERGY STAR certifies heat pumps under its Heat Pump Version 6.2 specification. Central air conditioners left the program in February 2026.

ENERGY STARSEER2EER2HSPF2
Split-system heat pump≥ 15.2≥ 11.0≥ 7.8
Single-package heat pump≥ 15.2≥ 10.0≥ 7.2
ENERGY STAR Heat Pump Version 6.2.
ENERGY STAR Cold ClimateSEER2HSPF2
Split, non-ducted (mini-split)≥ 15.2≥ 8.5
Split, ducted≥ 15.2≥ 8.1
Single package≥ 15.2≥ 8.1
Cold Climate has no EER2 requirement. Gas/electric package units are not eligible.

On top of those ratings, a Cold Climate heat pump has to show three things at low temperature:

  • COP at 5°F of at least 1.75.
  • Heating capacity at 5°F of at least 70% of its capacity at 47°F.
  • A controls verification: the unit has to reach those numbers running on its own controls, the way it would in a house — not in a forced test mode.

In the lookup

Every certified pair carries its own ENERGY STAR, Cold Climate and Most Efficient flags. Read the flag of the pair you are installing, not of the outdoor unit. Look up a model →Look up a model →

Where 47°F, 17°F and 5°F come from

They are the outdoor temperatures of the federal heating tests. The cooling ratings come from tests at 95°F and 82°F outdoors; the heating ratings from tests at 47°F, 35°F and 17°F, with an optional test at 5°F. Those are the points the certified capacities are measured at — nothing is measured in between.

How to read those points against your winter design temperature →

Tax credits and rebates in 2026

  • The federal §25C tax credit is over. It is not allowed for any property placed in service after December 31, 2025. An article offering “30%, up to $2,000, through 2032” describes the law before July 2025.
  • The Home Energy Rebates are run state by state. The two federal rebate programs were not repealed, and availability depends on the state. The Department of Energy points to each state energy office for status and eligibility.
  • Utility and state programs set their own thresholds, usually on the tiers above.

This is a report of what the rules say, not tax advice.